1. The type of smoke exhaust should be in accordance with the design. In addition to assume a smoke exhaust system can be partitioned, with ordinary open air outlets, the exhaust port shall be normally closed and have remote control on the remote control + metal tuyere.
2、手動(dòng)開啟裝置應(yīng)安裝在明顯位置且有消防標(biāo)志。
2, manual opening device should be installed in an obvious position, and there are fire signs.
3、排煙口執(zhí)行機(jī)構(gòu)安裝到位且排煙口的有效進(jìn)風(fēng)面積滿足設(shè)計(jì)要求。
3. The smoke exhaust port actuator is installed in place and the effective air intake area of the smoke exhaust port meets the design requirements.
4、排煙口安裝位置必須在高處安裝,少距地面不應(yīng)低于1.8米。
4, smoke exhaust port installation position must be installed at high altitude, at least away from the ground should not be less than 1.8 meters.
5、檢查防煙分區(qū)的設(shè)置、圍合是否滿足要求,排煙口是否安裝在相應(yīng)的防煙分區(qū)內(nèi)且與設(shè)計(jì)位置一致(位置變動(dòng)有可能保護(hù)距離大于30米)。
5, check whether the setting of the smoke prevention zone, whether the enclosure meets the requirements, whether the smoke discharge port is installed in the corresponding smoke prevention area, and consistent with the design position (location change, it is possible to protect the distance is greater than 30 meters).
1、風(fēng)口類型應(yīng)與設(shè)計(jì)一致。前室送風(fēng)除擔(dān)負(fù)2層以內(nèi)的正壓送風(fēng)系統(tǒng)可以用普通常開風(fēng)口外,其余均應(yīng)采用常閉且具備遠(yuǎn)程+就地控制的遠(yuǎn)控金屬風(fēng)口。樓梯間送風(fēng)一般采用自垂風(fēng)口等常開風(fēng)口。
1, tuyere type should be consistent with the design. Room air in addition to assume 2 layers within the positive pressure air supply system can be used in ordinary open wind estuary, the rest are normally closed and should be used with the remote control on the remote control + metal tuyere. The air supply in the stairwell usually adopts the self opening air inlet and so on.
2、檢查風(fēng)口的開啟狀態(tài)與設(shè)計(jì)一致(遠(yuǎn)控風(fēng)口平時(shí)均應(yīng)處于關(guān)閉狀態(tài))。
The open state is consistent with the design of 2, check the air (usually air remote control are to be in closed state).
3、執(zhí)行機(jī)構(gòu)安裝到位且不影響風(fēng)口的有效通風(fēng)面積。
3 、 the installation of the actuator is in place and does not affect the effective ventilation area of the air outlet.
4、檢查手動(dòng)開啟裝置手否在明顯位置且方便開啟。
4, check manual open device, hand no obvious position, and easy to open.
您的需求就是我們努力的方向,您的追求就是我們的追求,歡迎您的到,我們一起進(jìn)步,一起創(chuàng)新!
Your demand is the direction of our efforts, your pursuit is our pursuit, welcome you, and we progress together, together with innovation!